Endress+Hauser Hydrostatic Level measurement Deltapilot FMB50
Compact pressure sensor with the Contite measuring cell for hydrostatic level measurement
Description
Compact pressure sensor with the Contite measuring cell for hydrostatic level measurement
Specifications
Characteristic | Compact pressure transmitter for hydrostatic level measurement with flush mounted metallic Contite measuring cell: Hermetically sealed, condensate-resistant, climatic-proofed and with lowest temperature influences |
Supply voltage | 4…20 mA HART 10,5…45 VDC (Non Ex): Ex ia: 10,5…30 VDC PROFIBUS PA: 9…32 VDC (Non Ex) FOUNDATION Fieldbus: 9…32 VDC (Non Ex) |
Reference Accuracy | Standard 0.2 % Optional 0.1 % |
Long term stability | 0.05 % of URL/ year |
Process temperature | -10°C…100°C (14°F…212°F) |
Ambient temperature | -40°C…85°C (-40°F…185°F) |
Measuring cell | 100 mbar…10 bar (1.5 psi…150 psi) |
Smallest calibratable span | 10 mbar (1.45 psi) |
Vacuum resistance | 0 mbar abs. |
Max. Turn down | 100:1 |
Max. overpressure limit | 40 bar (600 psi) |
Process connection | Thread: G1 1/2, MNPT1 1/2 Flange: DN40…DN100, ASME 1 1/2″…4″, JIS 10K |
Process connection hygienic | Tri-Clamp DIN11851 DIN11864-1 NEUMO Varivent N SMS DRD |
Material process membrane | 316L, AlloyC Gold-Rhodium |
Material gasket | None, measuring cell welded |
Fill fluid | Inert oil, Synthetic oil |
Material housing | 316L, Die-cast aluminum |
Communication | 4…20 mA HART PROFIBUS PA FOUNDATION Fieldbus IO-Link |
Certificates / Approvals | ATEX, CSA, IECEx, JPN Ex, INMETRO, NEPSI, UK Ex |
Safety approvals | Overfill protection WHG SIL |
Design approvals | EN10204-3.1 NACE MR0103 |
Hygienic approvals | 3A, EHEDG CoC ASME-BPE |
Hygienic approvals | GL/ ABS/ LR/ BV/ DNV |
Drinking water approvals | KTW/ NSF/ ACS |
Specialities | Modularity to differential pressure and process pressure devices (replacable display, universal electronics) Diagnostic functions |
Specs at a glance
Pressure measuring range | 100 mbar…10 bar (1.5 psi…150 psi) |
Process pressure /
max. overpressure limit
|
40 bar (600 psi) |
Accuracy | Standard 0.2% Optional 0.1% |
Main wetted parts | Alloy C 316L optional coating AuPt |
Process temperature | -10°C…100°C (14°F…212°F) |
Max. measurement distance | 100m (328ft) H2O |
Material process membrane | 316L, AlloyC Gold-Rhodium |
Measuring cell | 100 mbar…10 bar (1.5 psi…150 psi) |
Field of application |
The compact Deltapilot FMB50 transmitter with the condensate resistant Contite measuring cell is typically used in the process and hygienic applications.
It is made for level measurement in liquid and paste-like media in open or closed containers and unaffected by possible foam formation. For use in SIL2 safety systems.
|
For level and/or pressure measurement |
|
Process connections | Thread, flanges and flush-mounted hygienic connections |
Temperature | –10 to +100°C (14 to 212°F) (+135°C (275°F) for 30 minutes maximum) |
Measuring range | 0.1 to 10bar (1.5 to 150psi) |
Accuracy | ±0.2%, ±0.1% (option) |
International explosion protection certificates | overfill prevention WHG, SIL, hygienic certificates |
Benefits |
Hermetically sealed Contite measuring cell with condensate-resistance, high reference accuracy: ±0.2%, optionally ±0.1% and minimum temperature effects
Modular concept for easy replacement of display or electronics
Seamless and independent system integration (HART/PA/FF)
Easy menu-guided commissioning via local display, 4 to 20mA with HART, PROFIBUS PA, FOUNDATION Fieldbus
|